Elite Suite ELT-KLED Manual de Instalação

Consulte online ou descarregue Manual de Instalação para Teclados numéricos Elite Suite ELT-KLED. Elite Suite ELT-KLED Installation manual [en] Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - ELT-KLED

ELT-KLED EliteSuite LED Keypad Installation Manual ELT-KLED EliteSuite Installation Manual

Página 2

Figure 9 - Slave Keypad Standard Zone Wiring PGM (Programmable Output) The EliteSuite LED Keypad uses a programmable output (PGM) that will acti

Página 3 - CONTENTS

Slave Reader Network The EliteSuite LED Keypad is capable of controlling a slave network of up to 8 proximity card reader devices from the followin

Página 4 - Hardware Compatibility

Slave Keypad Network The EliteSuite LED Keypad is capable of controlling a slave network of up to 4 other EliteSuite Keypads in Slave Mode (see D

Página 5 - Introduction

Indicator Lights The EliteSuite™ LED keypad features three status indicator lights showing the condition of the EliteSuite™ Security System.

Página 6 - Communication Connection

DEVICE CONFIGURATION Device Configuration Mode Access Before the EliteSuite LED Keypad module will communicate it must be assigned an address and

Página 7 - Zone Input Wiring

Device Options ([MENU] , [2]) The device options set options that relate to the mode of operation of the EliteSuite keypad. To enter the Device Op

Página 8 - Fire Zone Input Wiring

LOCAL INSTALLER LOGIN Introduction The default local installer code is [0000]. To access the local installation menu, press: [ENTER] , [0000]

Página 9 - Slave Keypad Zone Wiring

TIMING (MENU 1) ALL 3 Digits of the timer value MUST be entered when programming a timer. This means that for addresses below 100, you must enter [

Página 10 - PGM (Programmable Output)

Alarm/Siren ([MENU] , [1] , [3]) The siren/alarm timer is programmed from 000 to 250 minutes (Default 4 minutes). To program the timer value, p

Página 11 - Slave Reader Network

Reader Pre-Alarm Timer ([MENU] , [1] , [4]) The Reader Pre-Alarm Timer is programmable from 0 to 255 seconds (Default 30 Seconds). This is only used

Página 12 - Slave Keypad Network

PUBLICATION INFORMATION First Publication Draft Document Release Only Updated fire zone information Second Publication Option Menu Navigatio

Página 13 - Binary Number Display

OPTIONS (MENU 2)General Options ([MENU] , [2] , [1]) The general options set options that relate to the general operation of the EliteSuite keypa

Página 14 - DEVICE CONFIGURATION

6 Disabled no trouble beep will be generated. Option 4 - Device Power Up Disarmed 5 Enabled the system will power up disarmed regardless of the sys

Página 15

Arming Options ([MENU] , [2] , [2]) The arming options set functions that relate to the arming of the EliteSuite system. To enter the Arming Opti

Página 16 - LOCAL INSTALLER LOGIN

Reporting Options ([MENU] , [2] , [3]) The reporting options are a set of functions that relate to the reporting of information to the on site monito

Página 17 - TIMING (MENU 1)

Option 4 - Report Zone Fault 5 Enabled the system will report any zone fault trouble condition to the system controller. This will not indicate

Página 18

Panic Options ([MENU] , [2] , [4]) The panic options set functions that relate to the panic processing of the EliteSuite system. To enter the Panic

Página 19

Option 4 - User 8 Duress Code Enabled 5 Enabled the system will enable user code 8 to be a duress code user and on login will send a duress code

Página 20 - OPTIONS (MENU 2)

ZONES ([MENU] , [3]) Selecting a Zone To enter the Zone number selection menu, press [MENU] , [3] To select a zone to modify use the [Ï] and [Ð]

Página 21

Use this to set the zone type for a motion detector that is located in an entrance area. 4 Instant Zone will cause an alarm imm

Página 22

Option 3 - Force Zone 5 Enabled the zone can be force armed when it is not ready to be armed. A force armed zone will automatically be included in t

Página 23

CONTENTS INTRODUCTION ...1 Hardware Compatibility...

Página 24

CONTACT Contact Integrated Control Technology welcomes all feedback. Please go to our website or use the information below. Integrated Control

Página 26

Unit C, 6 Ascension Place, Mairangi Bay, P.O. Box 302-340 North Harbour, Auckland, New Zealand. Phone: +64 (9) 47

Página 27 - ([MENU] , [3])

INTRODUCTION This document details the wiring configuration of the EliteSuite condominium control keypad and installer programming functions. Ha

Página 28 - Zone Options

WIRING CONFIGURATION Introduction The wiring structure of the EliteSuite keypad uses an encrypted RS485 communication interface. Connections should b

Página 29

Communication Connection Support for up to 250 keypads per condominium controller is provided, connection to the system controller uses the netwo

Página 30 - Contact

Zone Input Wiring The EliteSuite LED Keypad is capable of connecting to 4 zone inputs, each zone input can then be programmed to perform the required

Página 31

Figure 6 - 4 Zone Input Duplex Mode (1K and 2K4) Fire Zone Input Wiring When wiring a zone to be a fire zone input the current programmed zone

Página 32

Slave Keypad Zone Wiring With one or more slave keypads connected, extra zones beyond the normal 4 are available on the suite system. There are 2 op

Comentários a estes Manuais

Sem comentários